|
Part
1 - Positive Pressure Testing
Description
Fire doors are tested by the Underwriters Laboratory (UL) and Warnock
Hersey (Intertek Testing Services) to ensure they provide adequate
protection of both life and property. The entire opening, including
hardware is tested.
Since
the fire test is designed to measure a door's ability to contain
the spread of fire, the possible acceleration of combustion and
breakdown of the door's ability to contain the fire could compromise
a previous rating and require some redesign of non-conforming products.
Thus, in 1997, the International Council of Building Officials (ICBO)
approved a change to the Uniform Building Code (UBC) that requires
fire doors be tested under positive pressure instead of neutral
pressure.With positive pressure testing, the neutral pressure plane
is lowered to a standard 40 inches above the finished floor, so
regardless of door height, the neutral pressure axis is defined
from the floor upward.
Most
recently, many code groups across the U.S. have adopted the International
Building Code (IBC), which also contains the requirement for positive
pressure testing.
Old
test method (UL 10B)
UL 10B test standard - Neutral pressure plane above the door
- Ambient air
is drawn into the test chamber around the entire door (top and
bottom)
- Hot air and
gasses are released by a damper
Historically,
the fire door test method placed the neutral pressure plane at the
top of the door, regardless of its overall height. Everything below
the top of the door was under negative pressure, and any gasses
or products of combustion were drawn into the test environment or
furnace.
With positive
pressure testing, the neutral pressure plane is lowered to a standard
40 inches above the finished floor. So, regardless of door height,
the neutral pressure axis is defined from the floor upward. The
effect of this change places a very gentle amount of pressure against
the remaining portion of the assembly, which may push smoke, hot
gasses and any potential flames around the perimeter of the door
assembly.
To envision
the difference, imagine a closed door with a fan pulling the air
away from the opening on the fire-side of the door. Now, reverse
the fan so it blows against the door. In either case, the pressure
isn't that great and certainly will not affect the structural integrity
of locks, latches, hinges or frame anchors. However, with the fan
blowing against the door, the products of combustion are not drawn
away as they were when the fan was pulling air away from the door.
If the face of a wood door is burning, the effect of positive pressure
is to enhance combustion somewhat, and to drive the smoke, gasses
and possibly flames through any leakage at the door perimeter. Under
the previous test, these products of combustion were carried away.
New
test method (UL 10C)
UL 10C test standard - Neutral pressure plane is 40 inches above
the finished floor
- Damper added
to control a neutral pressure plane at 40 inches above the finished
floor
- Ambient air
is drawn in from under the door
- Hot air and
gases are forced out at the top of the door
- No flame
detected on non-fire side of door for more than 10 seconds
To understand
how doors are now tested, let's go over the old test again. Air
was allowed to enter the room around the bottom and the top of the
door. All the positive pressure and heat that were built up in the
room were exhausted out of the top of the room. This is like opening
the damper all the way on your fireplace at home. No smoke or pressure
comes into the room, all the smoke and gas goes out the chimney.
So, if you think
of a closer (or a top latch of a vertical rod) mounted on the top
of the door, it is cooler than the other hardware located below
it because air is coming into the room from the outside and cooling
off the closer or latch. The neutral pressure plane, the plane of
separation between the positive and the negative pressure, is above
the door. Thus, none of the hardware was affected by the pressure
built up above the door. The hardware was only exposed to the heat
from the furnace jets, not from any pressure built up in the furnace.
In the new test,
a damper is added at the bottom of the furnace. Air is still allowed
to enter the fire at the bottom of the door, by the threshold. While
no air is allowed to enter at the top gap of the door, some air
is still allowed to exhaust by a damper. This is like your fireplace
at home with the damper opened about half way. Some smoke goes out
the chimney, but a lot of smoke and pressure comes back into the
room.
Similar to real
fire conditions, this is how the new test works. The neutral pressure
plane is established at 40 inches above the finished floor. This
is regulated by the amount of air that is released and entered into
the furnace through the dampers.
Actual fire
scenario
At the early stage of a fire, smoke and pressure forms at the top
of the room filling approximately 1/3 of the total space. Air to
fuel the fire is coming in from the bottom and top of the door.
Positive pressure builds up forming a neutral pressure plane. This
is the area between the positive pressure above the door and the
neutral pressure below the door.
Five minutes
into the fire, the fire is no longer confined to a small area. The
smoke, pressure and heat fills the space at about 40 inches above
the finished floor. Air is still coming into the room from under
the door, but air is no longer coming in from the top of the door.
The pressure has built up greatly, and with nowhere else to go,
it has to escape through the gap at the top of the door between
the door and frame.
In
the old test, the neutral pressure plane was leveled off above the
door, and none of the hardware was affected. With the new test,
this neutral plane is lowered to 40 inches above the finished floor,
and any hardware located above 40 inches is affected. And, while
some of the pressure and smoke will go out a window or ceiling tile,
most will go out the top of the door. This is why hardware located
40 inches above the finished floor is now more accurately affected
by the new test.
Evaluation
Upon submission, results of
your evaluation will be displayed with the correct answers shown
in red.
-
The UBC requires fire doors be tested under neutral pressure.
True
False
-
With positive pressure testing, the neutral pressure plane is _________________________________________.
At the top of the door, regardless of its overall height
Lowered to a standard 40 inches above the finished floor
Defined from the ceiling downward
-
With the new test, any hardware located above 40 inches is now affected.
True
False
-
The positive pressure testing method was designed to ___________________.
Measure a door's ability to contain the spread of fire
Regulate air flow
Emulate real fire conditions
All of the above
|